Thaum lub sij hawm AC test voltage, feem ntau siv ib feem ntawm qhov kev ntsuas tawm yog raws li hauv qab no:
(1) Qauv ua ntej kho
Ua ntej qhov kev xeem, tus qauv yuav tsum tau pretreated raws li cov kev cai muaj feem xyuam:
1. Khaws qhov chaw ntawm cov khoom kuaj kom huv si thiab qhuav kom tsis txhob muaj cov squares hauv zos uas tshwm sim los ntawm kev ya raws lossis muaj kuab paug rau ntawm qhov chaw insulating.
2. Thaum tsis muaj cov cai tshwj xeeb, cov qauv yuav tsum nyob ntawm qhov kub thiab txias thaum lub sijhawm kuaj.
3. Tom qab kev ua haujlwm ntawm cov khoom siv hluav taws xob, thermal lossis hluav taws xob dhau los, cov khoom kuaj yuav tsum tau tso tseg rau ib lub sijhawm ua ntej qhov kev xeem, thiaj li yuav txo tau qhov cuam tshuam ntawm cov ntsiab lus saum toj no ntawm cov txiaj ntsig kev xeem.
HV Hipot GDUI-311PD koob yees duab
(2) Txheeb xyuas qhov tso tawm ib nrab ntawm qhov ntsuas ntsuas nws tus kheej
Tsis txhob txuas cov khoom kuaj ua ntej, tab sis tsuas yog siv qhov hluav taws xob rau qhov ntsuas hluav taws xob.Yog tias tsis muaj qhov tso tawm ib nrab tshwm sim nyob rau hauv qhov ntsuas qhov ntsuas hluav taws xob me ntsis siab dua cov khoom kuaj, qhov ntsuas hluav taws xob tsim nyog;yog tias qhov kev cuam tshuam ib nrab ntawm qhov kev cuam tshuam ntau dhau los yog mus txog qhov siab tshaj plaws tso tawm qhov peev xwm ntawm cov khoom kuaj 50% ntawm tus nqi, lub hauv paus ntawm kev cuam tshuam yuav tsum raug txheeb xyuas thiab ntsuas los txo qis kev cuam tshuam.
(3) Calibration ntawm qhov ntsuas ntsuas
Lub ntsuas hluav taws xob hauv qhov ntsuas hluav taws xob yuav tsum tau ntsuas raws li niaj zaus ua ntej lub zog los txiav txim siab qhov ntsuas coefficient ntawm qhov ntsuas hluav taws xob thaum ntsuas cov khoom sib txuas.Qhov coefficient no cuam tshuam los ntawm cov yam ntxwv ntawm Circuit Court thiab capacitance ntawm cov khoom kuaj.
Nyob rau hauv lub calibrated Circuit Court rhiab heev, saib seb puas muaj kev cuam tshuam loj thaum lub high-voltage fais fab mov tsis txuas los yog tom qab lub high-voltage fais fab mov txuas, thiab yog tias muaj, sim tshem tawm nws.
(4) Kev txiav txim siab ntawm qhov tso tawm qhov hluav taws xob ib nrab thiab qhov hluav taws xob tua hluav taws xob
Tshem tawm lub calibration ntaus ntawv thiab khaws lwm cov xov hlau tsis hloov.Thaum lub waveform ntawm qhov ntsuas hluav taws xob ua tau raws li qhov yuav tsum tau ua, qhov hluav taws xob tau ntxiv los ntawm qhov hluav taws xob deb tshaj qhov xav tau ib feem ntawm qhov hluav taws xob hluav taws xob, thiab qhov hluav taws xob tau nce ntawm qhov ceev ceev kom txog thaum lub peev xwm tawm mus txog tus nqi teev.Lub voltage ntawm lub sij hawm no yog ib feem tawm inception voltage.Tom qab ntawd qhov hluav taws xob tau nce los ntawm 10%, thiab tom qab ntawd qhov hluav taws xob txo qis kom txog thaum lub peev xwm tawm tau sib npaug ntawm cov lus hais saum toj no, thiab qhov sib txuas ntawm qhov hluav taws xob yog qhov hluav taws xob ntawm ib nrab tawm.Thaum ntsuas, qhov siv hluav taws xob tsis raug tso cai kom dhau qhov ntsuas ntsuas qhov ntsuas qhov ntsuas ntawm qhov khoom ntsuas.Tsis tas li ntawd, rov ua daim ntawv thov ntawm qhov voltages ze rau nws yuav ua rau cov khoom kuaj puas.
(5) Ntsuas qhov tso tawm ib nrab raws li qhov ntsuas qhov ntsuas qhov ntsuas
Nws tuaj yeem pom los ntawm cov saum toj no hais tias cov kev ntsuas uas qhia txog ib feem ntawm qhov tso tawm tag nrho yog ntsuas ntawm ib qho hluav taws xob tshwj xeeb, uas tej zaum yuav siab dua qhov kev tawm qhov hluav taws xob ib nrab.Qee lub sij hawm nws tau teev tseg los ntsuas qhov muaj peev xwm tawm hauv ntau qhov kev ntsuas hluav taws xob, thiab qee zaum nws tau teev tseg kom tswj tau qee lub sijhawm nyob rau hauv qee qhov kev ntsuas hluav taws xob thiab ua ntau yam kev ntsuas los soj ntsuam qhov kev loj hlob ntawm ib feem tawm.Thaum ntsuas qhov paug tawm, nws tseem tuaj yeem ntsuas tus naj npawb ntawm cov paug tawm, qhov nruab nrab tawm tam sim no thiab lwm yam kev tso tawm ib nrab.
1. Kev ntsuas tsis tau ua ntej siv hluav taws xob
Thaum lub sij hawm xeem, qhov voltage ntawm tus qauv yog maj mam nce los ntawm tus nqi qis rau tus nqi teev, thiab khaws cia rau ib lub sij hawm ntawm lub sij hawm ua ntej ntsuas ib feem ntawm qhov paug tawm, ces txo qhov voltage thiab txiav tawm lub hwj chim mov.Qee lub sij hawm kev tso tawm ib nrab yog ntsuas thaum lub sij hawm voltage ramp-up, ramp-down, los yog thoob plaws lub sij hawm xeem ntawm lub voltage teev.
2. Kev ntsuas nrog pre-applied voltage
Thaum lub sij hawm kuaj, qhov voltage yog maj mam nce los ntawm tus nqi qis, thiab tom qab tshaj qhov teev ib feem ntawm qhov kev ntsuas hluav taws xob, nws nce mus rau qhov kev siv hluav taws xob ua ntej, tswj nws rau qee lub sijhawm, tom qab ntawd poob rau qhov ntsuas qhov ntsuas hluav taws xob, tuav lub sijhawm teev tseg, thiab tom qab ntawd ntsuas ntawm lub sijhawm ib ntus tso tawm ib nrab.Thaum lub sij hawm tag nrho lub sij hawm ntawm daim ntawv thov voltage, yuav tsum tau them nyiaj mloog mus rau qhov variation ntawm ib feem ntawm qhov tso tawm kom muaj nuj nqis.
Post lub sij hawm: Nov-16-2022