GDCO-301 Online Monitoring System ntawm Circulating Tam sim no ntawm Cable Sheath
Cov kab hluav taws xob siab tshaj 35kV feem ntau yog ib leeg-core cables nrog hlau sheath.Txij li cov hlau sheath ntawm ib leeg-core cable yog hinged nrog cov magnetic teb kab tsim los ntawm AC tam sim no nyob rau hauv cov tub ntxhais hlau, ob kawg ntawm ib tug tub ntxhais cable muaj ib tug high induced voltage.Yog li ntawd, kev ntsuas av tsim nyog yuav tsum tau coj los ua kom muaj qhov cuam tshuam ntawm qhov hluav taws xob muaj kev nyab xeeb (feem ntau tsis tshaj 50V, tab sis tsis pub ntau tshaj 100V nrog kev ntsuas kev nyab xeeb).Feem ntau, cov hlau sheath ntawm luv kab ib leeg-core cable yog grounded ncaj qha ntawm ib kawg thiab grounded los ntawm qhov sib txawv los yog tiv thaiv resistor ntawm lwm kawg.Cov hlau sheath ntawm kab ntev ib leeg - tub ntxhais cable yog grounded los ntawm peb - theem segmental cross - kev twb kev txuas.Tsis muaj teeb meem ntawm txoj kev hauv av twg yog txais yuav, zoo rwb thaiv tsev yog tsim nyog.Thaum lub rwb thaiv tsev ntawm lub cable puas lawm, cov hlau sheath yuav tsum grounded nyob rau hauv ntau lub ntsiab lus, uas yuav ua rau lub circulating tam sim no, ua rau kom poob ntawm sheath, cuam tshuam rau lub peev xwm nqa tam sim no ntawm lub cable, thiab txawm ua rau lub cable raug hlawv. vim overheat.Nyob rau tib lub sij hawm, lav lub high voltage cable hlau sheath grounding ncaj qha mus txuas qhov chaw kuj tseem ceeb heev, yog hais tias lub hauv paus ntsiab lus tsis tau zoo nyob rau hauv ntau yam yog vim li cas, lub cable hlau sheath tej zaum yuav nce sharply mus rau ob peb kilovolts txawm kaum tawm txhiab volts. , nws yog ib qho yooj yim uas yuav ua rau cov txheej sheath tawg thiab tas mus li tso tawm, ua rau qhov kub thiab txias ntawm cable txheej sheath los yog txawm hlawv.
GDCO-301 siv txoj kev circulating tam sim no.Thaum ib leeg-core cable hlau sheath yog nyob rau hauv ib txwm tej yam kev mob (ie, ib-point grounding), circulating tam sim no ntawm lub sheath, feem ntau capacitive tam sim no, yog heev me me.Thaum muaj ntau lub ntsiab lus earthing tshwm sim ntawm cov hlau sheath thiab tsim ib lub voj, circulating tam sim no yuav nce siab thiab tuaj yeem ncav cuag ntau dua 90% ntawm lub ntsiab tam sim no.Kev saib xyuas lub sijhawm tiag tiag ntawm cov hlau sheath ncig thiab nws cov kev hloov pauv tuaj yeem paub txog kev saib xyuas hauv online ntawm ntau lub ntiaj teb kev txhaum ntawm ib leeg-core cable hlau sheath, kom raws sij hawm thiab raug pom lub ntiaj teb txhaum, hauv paus tsis txhob tshwm sim ntawm cable sib tsoo thiab xyuas kom muaj kev nyab xeeb thiab txhim khu kev qha.
Nws siv GSM lossis RS485 ua hom kev sib txuas lus.Nws yog tsim rau multi-point hauv av txhaum xyuas ntawm ib tug tub ntxhais cables saum toj no 35kV.
GDCO-301 Online Monitoring System ntawm Circulating Tam sim no ntawm Cable Sheath suav nrog: chav tsev tseem ceeb ntawm kev saib xyuas cov cuab yeej thiab tam sim no transformer, kub thiab tiv thaiv tub sab sensor.Lub hom qhib tam sim no transformer yog ntsia rau hauv av kab ntawm cable sheath thiab yog hloov dua siab tshiab rau hauv ib tug thib ob teeb liab ua ntej lub soj ntsuam ntaus ntawv yog qhia.Lub ntsuas kub ntsuas yog siv los saib xyuas cov kab hluav taws xob kub, thiab cov khoom siv tiv thaiv tub sab yog siv los saib xyuas cov kab hauv av.Cov muaj pes tsawg leeg ntawm kev saib xyuas online ntawm cable sheath yog raws li hauv qab no:
●Kev saib xyuas hauv av tam sim no ntawm peb theem cable sheath, tag nrho hauv av tam sim no thiab kev khiav hauj lwm tam sim no ntawm txhua theem tseem ceeb cable;
●Real-time saib xyuas ntawm peb-theem cable kub;
●Real-time anti - tub sab saib xyuas ntawm cable sheath grounding;
●Lub sijhawm luv tuaj yeem teem caij;
●Tswb tsis tau thiab seb qhov kev soj ntsuam xyuas tsis raug tso cai los tsim lub tswb tuaj yeem teeb tsa;
●Teem tus nqi siab tshaj, yam tsawg kawg nkaus thiab tus nqi nruab nrab hauv lub sijhawm preset;
●Kev saib xyuas lub sijhawm tiag tiag ntawm qhov sib piv ntawm qhov siab tshaj plaws thiab qhov tsawg kawg nkaus ntawm ib theem hauv av tam sim no nyob rau hauv lub sijhawm txheeb cais, thiab kev ua haujlwm tswb;
●Kev saib xyuas lub sijhawm tiag tiag ntawm qhov piv ntawm cov av tam sim no kom thauj khoom hauv lub sijhawm txheeb xyuas, thiab kev ua haujlwm tswb;
●Kev saib xyuas lub sijhawm tiag tiag ntawm kev hloov pauv ntawm ib theem hauv av tam sim no nyob rau hauv lub sijhawm txheeb xyuas, thiab kev ua haujlwm tswb;
●Cov ntaub ntawv ntsuas tuaj yeem xa tuaj txhua lub sijhawm.
●Muaj peev xwm qhia ib lossis ntau qhov kev saib xyuas rau lub tswb, xa cov ntaub ntawv ceeb toom rau lub xov tooj ntawm tes;
●Real-time ntsuas ntawm input voltage;
●Txhua cov ntaub ntawv soj ntsuam muaj cov ntawv sau sijhawm los xyuas kom meej qhov tsis zoo ntawm cov ntaub ntawv;
●Txhua qhov kev soj ntsuam sensors tuaj yeem teeb tsa raws li cov neeg siv khoom xav tau;
●Ntau cov ntaub ntawv kis tau tus mob: RS485 interface, GPRS, GSM SMS, tuaj yeem siv ib lossis ntau hom kev sib kis ntawm tib lub sijhawm;
●Txhawb nqa tej thaj chaw deb tu thiab txhim kho;
●Kev siv hluav taws xob tsawg tsim, txhawb ntau lub zog tawm tswv yim: CT induction zog, AC-DC lub zog thiab roj teeb lub zog;
●Nrog rau qib kev lag luam, nrog kev ntseeg tau zoo & ruaj khov;
●Modular tag nrho cov qauv tsim, yooj yim rau nruab, ntsuas ntsuas tau coj los ntawm txhua qhov chaw, kev ua haujlwm zoo los tiv thaiv kev vibration, thiab yooj yim los hloov thiab disassemble;
●Txhawb IP68 tiv thaiv qib.
Yam khoom | Tsis muaj | |
Tam sim no
| Ua haujlwm tam sim no | 1 channel, 0.5~1000A (tuaj yeem kho tau) |
Sheath hauv av tam sim no | 4 channel, 0.5~200A (tuaj yeem kho tau) | |
Kev ntsuas qhov tseeb | ± (1% + 0.2A) | |
Lub sijhawm ntsuas | 5~200s | |
Kub | Ntau yam | -20 ℃~+180 ℃ |
Qhov tseeb | ± 1 ℃ | |
Lub sijhawm ntsuas | 10~200s |
RS485 chaw nres nkoj
●Baud tus nqi: 2400bps, 9600bps thiab 19200bps tuaj yeem teeb tsa.
●Cov ntaub ntawv ntev: 8 ntsis:
●Pib me ntsis: 1 ntsis;
●Nres me ntsis: 1 ntsis;
●Calibration: tsis muaj calibration;
GSM / GPRS chaw nres nkoj
●Ua haujlwm zaus: Quad-band, 850 MHz / 900 MHz / 1800 MHz / 1900 MHz;
●GSM Lus Suav / Lus Askiv luv luv;
●GPRS chav kawm 10, Max.Download ceev 85.6 kbit / s, Max.upload ceev 42.8 kbit / s, txhawb TCP / IP, FTP thiab HTTP raws tu qauv.
Fais fab mov
AC fais fab mov
●Voltage: 85 ~ 264VAC;
●Zaus: 47 ~ 63Hz;
●Lub zog: ≤8W
Roj teeb
●Voltage: 6VDC
●Peev Xwm: txiav txim siab los ntawm lub sijhawm ua haujlwm tsis tu ncua ntawm roj teeb
●Roj teeb compatibility
Electrostatic paug tiv thaiv kab mob | Chav Kawm 4:GB/T 17626.2 |
Xov tooj cua zaus electro-magnetic teb hluav taws xob tiv thaiv kab mob | Chav Kawm 3:GB/T 17626.3 |
Hluav taws xob nrawm nrawm / tawg tiv thaiv | Chav Kawm 4:GB/T 17626.4 |
Kev tiv thaiv kab mob | Chav Kawm 4:GB/T 17626.5 |
Xov tooj cua zaus teb inductive conduction tiv thaiv | Chav Kawm 3:GB/T 17626.6 |
Fais fab zaus magnetic teb tiv thaiv | Chav Kawm 5:GB/T 17626.8 |
Pulse magnetic teb tiv thaiv kab mob | Chav Kawm 5:GB/T 17626.9 |
Damping oscillation magnetic teb tiv thaiv | Chav Kawm 5:GB/T 17626.10 |
Daim ntawv pov thawj:
Q / GDW 11223-2014: Technical Specification rau lub xeev nrhiav kom tau cov kab hluav taws xob siab
4.1 Cable lub xeev kuaj pom tau muab faib ua ob pawg: kev tshawb nrhiav online thiab kev tshawb nrhiav offline.Cov qub suav nrog kev tshawb nrhiav infrared, kev tshawb pom hauv av tam sim no ntawm cable sheath, ib nrab tso tawm kom pom, thaum lub sijhawm offline nrhiav pom muaj qee qhov paug tawm hauv qab qhov sib txawv zaus series resonant test, oscillation cable ib nrab tso tawm kom pom.
4.2 Cable lub xeev kev kuaj xyuas hom muaj xws li kev sim dav dav ntawm qhov loj me, rov kuaj dua ntawm cov teeb meem xav tau, kuaj tsom rau cov khoom siv tsis raug.Nyob rau hauv txoj kev no, cable ib txwm ua haujlwm tuaj yeem lav.
4.3 Cov neeg ua haujlwm tshawb nrhiav yuav tsum tuaj koom kev cob qhia kev tshawb nrhiav cable thiab tuav qee daim ntawv pov thawj.
4.4 Basic yuav tsum tau ntawm lub davhlau ya nyob twg infrared imager thiab av tam sim no detector xa mus rau Appendix A. Basic yuav tsum tau ntawm high voltage ib feem paug ntes, ultra high voltage ib feem paug ntes thiab ultrasonic ib feem paug ntes xa mus rau Q / GDW11224-2014.
4.5 Ntau yam ntawm daim ntawv thov yog hais txog Table 1.
Txoj kev | Voltage qib ntawm cable | Qhov tseem ceeb nrhiav pom | Tsis zoo | Online / offline | Lus hais |
Thermal infrared duab | 35kV thiab siab dua | Terminal, connector | Kev sib txuas tsis zoo, damped, rwb thaiv tsev flaw | Online | Kev yuam cai |
Hlau sheath hauv av tam sim no | 110kV thiab siab dua | Grounding system | Rwb thaiv tsev flaw | Online | Kev yuam cai |
High zaus ib nrab tso tawm | 110kV thiab siab dua | Terminal, connector | Rwb thaiv tsev flaw | Online | Kev yuam cai |
Ultra siab zaus ib feem tso tawm | 110kV thiab siab dua | Terminal, connector | Rwb thaiv tsev flaw | Online | xaiv tau |
Ultrasonic yoj | 110kV thiab siab dua | Terminal, connector | Rwb thaiv tsev flaw | Online | xaiv tau |
Kev tso tawm ib nrab nyob rau hauv qhov sib txawv zaus series resonant test | 110kV thiab siab dua | Terminal, connector | Rwb thaiv tsev flaw | Offline | Kev yuam cai |
OWTS oscillation cable ib nrab tso tawm | 35kv ua | Terminal, connector | Rwb thaiv tsev flaw | Offline | Kev yuam cai |
Table 1
Qib voltage | Lub sijhawm | Lus hais |
110 (66) kV | 1. Tsis pub dhau 1 lub hlis tom qab kev ua haujlwm lossis kev kho loj 2. Ib zaug rau lwm 3 lub hlis 3. Yog xav tau | 1. Lub sij hawm kuaj xyuas yuav tsum luv luv thaum muaj qhov hnyav ntawm cov kab hluav taws xob lossis lub caij ntuj sov siab. 2. Kev kuaj xyuas yuav tsum tau ua ntau zaus raws li qhov chaw ua haujlwm tsis zoo, cov khoom siv tsis zoo, thiab cov khoom siv tsis raug. 3. Kev kho kom zoo yuav tsum tau ua raws li cov khoom siv thiab ib puag ncig ua haujlwm. 4. Kev saib xyuas hauv online ntawm cov av tam sim no ntawm cable sheath tuaj yeem hloov nws qhov kev tshawb pom nyob. |
220 kV ua | 1. Tsis pub dhau 1 lub hlis tom qab kev ua haujlwm lossis kev kho loj 2. Ib zaug rau lwm 3 lub hlis 3. Yog xav tau | |
500kV ua | 1. Tsis pub dhau 1 lub hlis tom qab kev ua haujlwm lossis kev kho loj 2. Ib zaug rau lwm 3 lub hlis 3. Yog xav tau |
Rooj 4
5.2.3 Cov txheej txheem kuaj mob
Nws yog ib qho tsim nyog los ua ke cov load ntawm cable thiab txawv txav tam sim no ntawm cable sheath nrog ntsuas cov ntaub ntawv ntawm cable sheath.
Cov txheej txheem kuaj mob hais txog Table 5.
Kuaj | Kev tshwm sim | Tswv yim |
Yog tias tag nrho cov kev xav tau hauv qab no tau ua tiav: 1. Tus nqi ntawm av tam sim no<50A; 2. Qhov piv ntawm av tam sim no thiab load<20% yog '; 3. Max.tus nqi / Min.tus nqi ntawm ib theem av tam sim no<3 | Ib txwm | Ua haujlwm li qub |
Yog tias muaj kev xav tau hauv qab no tau ntsib: 1. 50A≤ tus nqi ntawm av tam sim no ≤100A; 2. 20% ≤ qhov piv ntawm av tam sim no thiab load ≤50%; 3. 3 ≤Max.tus nqi/Min.tus nqi ntawm ib theem av tam sim no≤5; | Ceev faj | Txhim khu kev soj ntsuam thiab txo lub sij hawm nrhiav kom pom |
Yog tias muaj kev xav tau hauv qab no tau ntsib: 1. Tus nqi ntawm av tam sim no>100A; 2. Qhov piv ntawm av tam sim no thiab load>50% yog '; 3. Max.tus nqi/Min.tus nqi ntawm ib theem av tam sim no>5 | Tsis zoo | Fais fab tuag thiab kos. |
Table 5